November 5, 2025
Undersized ("A small horse pulling a heavy cart"): The boiler runs at full capacity constantly but still fails to reach the desired temperature. The room stays cold, the equipment suffers from excessive wear and tear, and it ironically uses more electricity.
Oversized ("A large horse pulling a small cart"):
Higher purchase cost.
Short Cycling: After reaching the set temperature, a powerful boiler shuts off quickly, only to restart shortly after when the temperature drops slightly. This frequent on/off cycling wears out components, reduces lifespan, and increases energy consumption.
Less economical operation.
The Golden Rule: Match the power to your precise needs.
Selecting the correct power for an electric boiler requires a comprehensive evaluation of these 5 key factors:
Heated Area (Core Factor): The total floor area of the space is the foundation for all calculations.
Building Insulation (Critical Variable):
Old Building/Poor Insulation: Poor heat retention requires higher power.
New Building/Well-Insulated: Good heat retention allows for lower power.
Windows, Doors & Air Tightness: Single-pane windows and poorly sealed doors significantly increase heat loss.
Regional Climate (Environmental Factor):
Severe Cold Regions (e.g., Heilongjiang, Jilin): Very low winter temperatures demand high heat output.
Cold Regions (e.g., Jiangsu, Hubei): Humid cold, but temperatures are milder than the far north.
Reference your local "Outdoor Heating Design Temperature."
Room/Ceiling Height: Higher ceilings mean a larger volume of air to heat, requiring more power.
Type of Heating Emitters:
Radiant Floor Heating: Operates at lower temperatures (typically 35-50°C) continuously, requiring relatively less power.
Radiators: Operate at high temperatures (typically 60-80°C), requiring relatively more power.
Fan Coils: Heat up quickly; power requirements are similar to or slightly higher than radiators.
Here are two methods: a Quick Estimate and a Detailed Calculation.
A rule-of-thumb based on experience, assuming standard ceiling heights (~2.8m) and reasonable insulation.
Power (kW) ≈ Heated Area (m²) × Heat Load per Unit Area (W/m²)
How to choose the "Heat Load per Unit Area"?
Well-Insulated New Build: 60 - 80 W/m²
Average Apartment/Average Insulation: 80 - 100 W/m²
Old House/Poor Insulation: 100 - 120 W/m²
Self-built Villa/High Ceilings/Large Windows: 120 - 150 W/m²
Example: A 100 m² average apartment in Beijing with average insulation. Power ≈ 100 m² × 100 W/m² = 10,000 W = 10 kW Therefore, a 10kW - 12kW electric boiler would be suitable.
This is a more professional HVAC method that accounts for more variables.
Formula: Heat Load Q = V × ΔT × K / 860
Q: Total Heat Load (kW)
V: Volume of the space (Length × Width × Height, in m³)
ΔT: Design Temperature Difference (℃)
Indoor Design Temp.: Typically 18°C - 20°C
Outdoor Design Temp.: Check local HVAC design standards (e.g., Beijing ≈ -7.6°C, Harbin ≈ -26°C)
ΔT = Indoor Temp. - Outdoor Temp.
K: Building's Overall Heat Transfer Coefficient (W/m²·K), related to insulation.
Excellent Insulation: 0.3 - 0.4
Good Insulation: 0.5 - 0.6
Average Insulation: 0.7 - 0.9
Poor Insulation: 1.0 - 1.5
860: Unit conversion factor (1 kW = 860 kcal/h)
Example (Simplified):
Space: 100 m², Ceiling Height 2.8m, Volume V = 280 m³
Location: Zhengzhou, Outdoor Design Temp. = -3°C
Indoor Target: 20°C → ΔT = 20 - (-3) = 23°C
Insulation: Average, use K = 0.8
Calculation: Q = 280 × 23 × 0.8 / 860 ≈ 6 kW
This result is lower than the quick estimate because it more scientifically considers volume and specific temperature difference. In practice, a safety margin of 10%-20% is typically added to cope with extreme weather and ensure a faster heat-up time. Final Power = 6 kW × 1.2 = 7.2 kW → An 8kW boiler should be selected.
| Heated Area (m²) | Good Insulation (kW) | Avg. Insulation (kW) | Poor Insulation (kW) | Example Property Type |
|---|---|---|---|---|
| Up to 60 m² | 4 - 6 kW | 6 - 8 kW | 8 - 10 kW | One-Bedroom Apartment |
| 60 - 100 m² | 6 - 8 kW | 8 - 12 kW | 12 - 15 kW | Two-Bedroom Apartment |
| 100 - 150 m² | 8 - 12 kW | 12 - 18 kW | 18 - 24 kW | Three-Bedroom Flat |
| 150 - 200 m² | 12 - 16 kW | 16 - 24 kW | 24 - 30 kW | Large Flat / Small Villa |
| 200 m²+ | Professional calculation required. Often needs multiple units or a high-power commercial model. | Detached Villa |
Final Important Note: The power requirement for instant domestic hot water (DHW) is a separate and often much higher calculation. If you want the electric boiler to provide both space heating and DHW, the power must be sized to meet the DHW demand